Program locations 24 through 36 are used differently
for the particular Phone Format Chosen (see Address
38, 39). If Zone Doubling is selected in Address 55,
Fire and Tamper reports are programmed in
Addresses 56 and 57 for Zones 7 and 8.
If a value of 00 is programmed in any of these
locations the panel will not send that particular
report.
Pulsed Formats
(3/1, 3/1E, 3/1 with Parity, 3/1E
with Parity, 4/1, and 4/2) will need a unique value
placed at each address location. Please note that
each Central Station receiver differs slightly in the
report codes that it expects. Therefore, it is best to
verify the codes you use with the Central Station.
Some of the reports that can be sent, such as
OPEN, CLOSE, PARTIAL CLOSE can send an
associated User Number as the second digit. To
accomplish this, program an F (*5) as the second
digit in the program location. When the report is
sent the panel will replace the F with the
appropriate user number. Pulsed formats 3/1, 3/1
with Parity, and 4/1 need a 0 for the second digit
and cannot send user numbers. A non-zero in the
second digit location indicates an extended 3/1E or
4/1E format.
Fixed Report Formats
(Contact ID, SIA, 4/9) have
well defined reports that are sent regardless of the
value programmed in the report code location. Any
non-zero value programmed in the report code
location will send the appropriate report.
Special Formats
(Personal Dialing Format, Pager)
are not recommended for primary reporting. If they
are used, Personal Dialing Format could use the
same report codes as the Pulsed Formats. Pager
has a limitation in that it can’t use the Hex values A
(*0), B (*1), C (*2), D (*3), E (*4), F (*5). These
values can not be passed on to a Numeric Pager.
Keypad Fire Report:
This report is sent when a
fire alarm has been activated using the “A”
emergency key.
Keypad Fire Restoral Report:
This report is sent
when a keypad fire alarm has been restored using
the [System Reset] command.
Keypad Help Alarm Report:
This report is sent
when an help alarm has been activated using the
“B” emergency key.
Keypad Panic Report:
This report is sent when
an emergency alarm has been activated using the
“C” emergency key.
Zone Alarm:
An alarm report is sent when a zone
alarm occurs. Program this report for any zones
where an alarm report is desired. For local zones
(no reports), replace the default value with 00.
Zone Alarm Restoral:
This report is sent when
the zone alarm is cleared. Refer to Address 07 for
exact point at which report will be sent.